Brookdale Olympia West: inspection reports

The DSHS record for Brookdale Olympia West in Olympia, WA: every visit in the last three years, with each citation in the inspector’s own words. Back to the profile and its summaries.

Full record

8 visits, most recent first.

2025-09-01Complaint Investigation1 finding

Plain-language summary

A complaint investigation at Brookdale Olympia West found that the facility did not conduct proper investigations after two residents sustained injuries of unknown origin in July and August 2025—including bilateral wrist bruising for one resident and a skin tear for another—and facility staff acknowledged they did not complete incident reports, written investigation summaries, or documented resident and staff interviews for these incidents. The facility could not rule out the possibility of abuse or neglect because no formal investigations were performed. A deficiency was cited for failing to maintain written records of investigations as required by Washington regulations.

Type AWAC §WAC 388-78A-2050
Verbatim citation text · WAC §WAC 388-78A-2050

“The facility failed to conduct proper investigations for injuries of unknown origin involving Resident 1 (bruising on 07/26/2025 and skin tear on 08/04/2025). No written incident reports, investigation summaries, or documented resident/staff interviews were completed despite two separate unexplained injuries.”

Read raw inspector notes

WAC 388-78A-2050: The facility failed to conduct proper investigations for injuries of unknown origin involving Resident 1 (bruising on 07/26/2025 and skin tear on 08/04/2025). No written incident reports, investigation summaries, or documented resident/staff interviews were completed despite two separate unexplained injuries. WAC 388-78A-2050: The facility failed to conduct proper investigations for an injury of unknown origin involving Resident 2 (skin tear and bruising on 07/26/2025). While an incident report was filed, no investigation was conducted and no written summary or documented interviews were completed to rule out abuse or neglect. WAC 388-78A-2050: The facility does not maintain a system for documenting investigations of incidents of unknown origin. Staff indicated they do not complete written summaries of investigations and do not document resident or staff interviews, failing to maintain written records as required by regulation.

2024-12-01Complaint Investigation2 findings

Plain-language summary

A complaint investigation at Brookdale Olympia West in June 2024 found that two of four community showers failed to provide adequate hot water or water pressure, with temperatures measured as low as 67°F, and the facility's water temperature policy did not comply with state requirements; a citation was issued for these deficiencies. A separate allegation of missing resident clothing and blankets could not be substantiated, as the facility was actively searching for items and had already recovered several pieces. The facility was ordered to correct these violations to maintain its license.

Type AWAC §WAC 388-78A-2950
Verbatim citation text · WAC §WAC 388-78A-2950

“The facility failed to ensure water temperatures met requirements, with temperatures both below the minimum of 105°F (as low as 60°F) and exceeding the maximum of 120°F (as high as 130°F) at various sinks, bathtubs, and shower fixtures used by residents.”

Type AWAC §WAC 388-78A-2600
Verbatim citation text · WAC §WAC 388-78A-2600

“The facility's water temperature policy was not in compliance with state law, as evidenced by the failure to maintain water temperatures within the required 105°F to 120°F range specified in WAC 388-78A-2950.”

Read raw inspector notes

WAC 388-78A-2950: The facility failed to ensure water temperatures met requirements, with temperatures both below the minimum of 105°F (as low as 60°F) and exceeding the maximum of 120°F (as high as 130°F) at various sinks, bathtubs, and shower fixtures used by residents. WAC 388-78A-2600: The facility's water temperature policy was not in compliance with state law, as evidenced by the failure to maintain water temperatures within the required 105°F to 120°F range specified in WAC 388-78A-2950.

2024-10-01Complaint Investigation3 findings

Plain-language summary

A complaint investigation at Brookdale Olympia West from July 2024 found that the facility failed to provide resident showers as required by service agreements due to insufficient staffing, a finding confirmed through staff interviews, direct observation, and review of shower documentation. A citation was issued for this failed provider practice. The investigation included interviews with staff and family members, observation of five residents and facility operations, and review of policies and resident service plans.

WAC §__wa_e499f09e71003314df9859b209f2d03b
Verbatim citation text · WAC §__wa_e499f09e71003314df9859b209f2d03b

“Facility out of compliance with water temperatures in resident showers. Cold water temperatures identified as a physical environment deficiency.”

WAC §__wa_240a20ecbb13c34a8988aa7ac4e43267
Verbatim citation text · WAC §__wa_240a20ecbb13c34a8988aa7ac4e43267

“Facility management instructed staff to pour cold water over a resident after water pressure and temperature decreased during a shower, causing the resident discomfort. Multiple staff interviews confirmed staff were following management instructions.”

WAC §__wa_4ef391efd31f809e7f56ea7aea245013
Verbatim citation text · WAC §__wa_4ef391efd31f809e7f56ea7aea245013

“Facility failed to provide resident showers as per the negotiated service agreement due to lack of staff. This deficiency was confirmed through staff interviews, observation, and document review.”

Read raw inspector notes

—: Facility out of compliance with water temperatures in resident showers. Cold water temperatures identified as a physical environment deficiency. —: Facility management instructed staff to pour cold water over a resident after water pressure and temperature decreased during a shower, causing the resident discomfort. Multiple staff interviews confirmed staff were following management instructions. —: Facility failed to provide resident showers as per the negotiated service agreement due to lack of staff. This deficiency was confirmed through staff interviews, observation, and document review.

2024-09-01Annual Compliance Visit1 finding

Plain-language summary

During a follow-up inspection on July 8, 2024, Brookdale Olympia West was found not in compliance with fire safety regulations: the facility failed to ensure all fire extinguishers had service tags documenting when they were serviced and checked, and failed to ensure all extinguishers were serviced yearly. This deficiency placed all 42 residents, staff, and visitors at risk of harm during a fire.

Type AWAC §WAC 388-78A-2040
Verbatim citation text · WAC §WAC 388-78A-2040

“The facility failed to ensure that all fire extinguishers had service tags showing when they were serviced and checked, and failed to ensure that all fire extinguishers were serviced yearly. Multiple fire extinguishers were last serviced in May 2024 with no monthly checks completed for June 2024. This placed all 42 residents, staff, and visitors at risk of harm during a fire.”

Read raw inspector notes

WAC 388-78A-2040: The facility failed to ensure that all fire extinguishers had service tags showing when they were serviced and checked, and failed to ensure that all fire extinguishers were serviced yearly. Multiple fire extinguishers were last serviced in May 2024 with no monthly checks completed for June 2024. This placed all 42 residents, staff, and visitors at risk of harm during a fire.

2024-07-01Complaint Investigation1 finding

Plain-language summary

On this complaint investigation, the Washington Department of Social and Health Services file includes this account: Staff falsely recorded temperature readings on logs, including temperatures added retroactively on 05/02/2024 for review on 05/03/2024, despite not performing actual temperature checks.

WAC §__wa_6fb4caccb534d0596e6772075d9679e3
Verbatim citation text · WAC §__wa_6fb4caccb534d0596e6772075d9679e3

“Kitchen staff documented freezer temperatures that were not actually checked. Staff falsely recorded temperature readings on logs, including temperatures added retroactively on 05/02/2024 for review on 05/03/2024, despite not performing actual temperature checks.”

Read raw inspector notes

—: Kitchen staff documented freezer temperatures that were not actually checked. Staff falsely recorded temperature readings on logs, including temperatures added retroactively on 05/02/2024 for review on 05/03/2024, despite not performing actual temperature checks.

2024-05-01Annual Compliance Visit1 finding

Plain-language summary

A routine inspection in February 2024 found that the facility was not in compliance with nurse delegation requirements, specifically that four of six medication technicians on staff lacked required credentials, training certifications, and state verification—including one whose nursing assistant registration had expired in 2019. The facility was also missing required documentation showing that registered nurses had verified staff qualifications and completed mandatory evaluations and supervision of delegated nursing tasks. The administrator signed a plan to correct these deficiencies by January 28, 2024.

Type AWAC §WAC 388-78A-2320
Verbatim citation text · WAC §WAC 388-78A-2320

“The facility failed to ensure staff had required nurse delegation training, supervision, and documentation by the Registered Nurse Delegator for 4 of 4 sampled residents (R1, R2, R3, R4) receiving nurse delegated services. Staff credentials and trainings were not verified prior to administering nurse delegated tasks, and unqualified and untrained staff administered medication services, placing residents at risk.”

Read raw inspector notes

WAC 388-78A-2320: The facility failed to ensure staff had required nurse delegation training, supervision, and documentation by the Registered Nurse Delegator for 4 of 4 sampled residents (R1, R2, R3, R4) receiving nurse delegated services. Staff credentials and trainings were not verified prior to administering nurse delegated tasks, and unqualified and untrained staff administered medication services, placing residents at risk.

2024-04-01Complaint InvestigationNo findings

Plain-language summary

This complaint investigation is in the Washington Department of Social and Health Services public file. No citation text was included for this visit.

2023-12-01Complaint Investigation3 findings

Plain-language summary

A complaint investigation at Brookdale Olympia West on August 14, 2023, found that the facility failed to complete an incident report promptly when a resident fell with injury in the community, which delayed family notification and resident care. A separate investigation the same day found the facility also failed to notify the Complaint Resolution Unit in a timely manner following a resident-to-resident altercation, as required by policy. Deficiencies were cited for both failures.

WAC §__wa_a4fc15df5c3361da17d8d597f058b79b
Verbatim citation text · WAC §__wa_a4fc15df5c3361da17d8d597f058b79b

“Facility failed to follow the care plan as per the negotiated service agreement and failed to notify the Complaint Resolution Unit timely, as per their policy, following a resident fall with injury in the community.”

WAC §__wa_6f5b5614d575c076787a0cafb55f1f90
Verbatim citation text · WAC §__wa_6f5b5614d575c076787a0cafb55f1f90

“Facility failed to complete an incident report at the time of the incident as per policy, resulting in family not being notified timely and delay of resident care following a resident fall with injury in the community.”

WAC §__wa_4b681f8933b7229f37e5773ccc292cce
Verbatim citation text · WAC §__wa_4b681f8933b7229f37e5773ccc292cce

“Facility failed to notify the Complaint Resolution Unit timely after a resident-to-resident altercation incident occurred as per their policy.”

Read raw inspector notes

—: Facility failed to follow the care plan as per the negotiated service agreement and failed to notify the Complaint Resolution Unit timely, as per their policy, following a resident fall with injury in the community. —: Facility failed to complete an incident report at the time of the incident as per policy, resulting in family not being notified timely and delay of resident care following a resident fall with injury in the community. —: Facility failed to notify the Complaint Resolution Unit timely after a resident-to-resident altercation incident occurred as per their policy.