The DLBC record for Abbington Manor Memory Care in Lehi, UT: every visit in the last three years, with each citation in the inspector’s own words. Back to the profile and its summaries.

Full record

4 visits, most recent first.

2026-03-11Follow-up visitNo findings

Plain-language summary

This follow-up visit is in the Utah Department of Health and Human Services public file. No citation text was included for this visit.

2026-02-24Follow-up visit1 finding

Plain-language summary

During an annual licensing inspection, inspectors found that hot water in the shower rooms exceeded the safe temperature limit set by Utah regulations, measuring between 132 and 142 degrees Fahrenheit on multiple tests. This same violation had been cited previously on February 2, 2026, and remained uncorrected at the time of this inspection. The facility was in noncompliance with the water temperature requirement under Rule R432-270-24(5).

SeriousR432-270-24(5)(a)-(b)Repeat
Verbatim citation text · R432-270-24(5)(a)-(b)

“The licensee was out of compliance with R432-270-24(5). During the environmental inspection, the shower rooms were accessed through an open door on the West side of the building. The water temperature was tested and it measured 132.1 degrees Fahrenheit. The water temperature was measured two more times throughout the inspection and it was measured to be 137.4 degrees Fahrenheit and 142.4 degrees Fahrenheit. This was previously cited on February 2, 2026.”

The state's follow-up

On March 11, 2026, the licensor verified that the hot water temperature was maintained between 105-120 degrees Fahrenheit, as stated in rule.

Read raw inspector notes

[R432-270-24(5)(a)-(b)] The licensee was out of compliance with R432-270-24(5). During the environmental inspection, the shower rooms were accessed through an open door on the West side of the building. The water temperature was tested and it measured 132.1 degrees Fahrenheit. The water temperature was measured two more times throughout the inspection and it was measured to be 137.4 degrees Fahrenheit and 142.4 degrees Fahrenheit. This was previously cited on February 2, 2026.

2026-02-02Annual Compliance Visit1 finding

Plain-language summary

During this annual inspection, the facility was found to be out of compliance with water temperature requirements in the shower room. Testing on multiple occasions throughout the day found water temperatures ranging from 151.6 to 154.1 degrees Fahrenheit, which exceeded the safe maximum. The facility must correct this noncompliance to ensure resident safety.

SeriousR432-270-24(5)(a)-(b)
Verbatim citation text · R432-270-24(5)(a)-(b)

“The licensee was out of compliance with R432-270-24(5)(b). During the inspection, an environmental tour of the facility was conducted and the shower room was accessed through an open door. The water temperature was tested and it measured 151.6 Fahrenheit (F). The water temperature was measured two additional times throughout the day and it measured 154.1 and 152.3 Fahrenheit.”

The state's follow-up

On March 11, 2026, the licensor verified that the hot water temperature was maintained between 105-120 degrees Fahrenheit, as stated in rule.

Read raw inspector notes

[R432-270-24(5)(a)-(b)] The licensee was out of compliance with R432-270-24(5)(b). During the inspection, an environmental tour of the facility was conducted and the shower room was accessed through an open door. The water temperature was tested and it measured 151.6 Fahrenheit (F). The water temperature was measured two additional times throughout the day and it measured 154.1 and 152.3 Fahrenheit.

2024-01-03Annual Compliance VisitNo findings

Plain-language summary

This annual visit is in the Utah Department of Health and Human Services public file. No citation text was included for this visit.

Source: Utah Dept. of Health & Human Services · Division of Licensing and Background Checks. DLBC inspection portal →