Heritage House Morton: inspection reports

The DSHS record for Heritage House Morton in Morton, WA: every visit in the last three years, with each citation in the inspector’s own words. Back to the profile and its summaries.

Full record

2 visits, most recent first.

2025-05-01Complaint Investigation6 findings

Plain-language summary

A complaint investigation found that Heritage House Morton failed to maintain fire safety systems and documentation as required by Washington state fire marshal regulations, including missing annual inspections of fire-resistant construction, fire doors with excessive gaps, a fire alarm panel breaker without a lock device, and incomplete fire drill records for night shifts. These failures placed all 30 residents, staff, and visitors at risk in the event of a fire. The facility received citations and was required to submit a plan of correction, though follow-up inspections in September and November 2024 found that several violations had not yet been corrected.

Type AWAC §WAC 212-12-044
Verbatim citation text · WAC §WAC 212-12-044

“Facility failed to provide records of night shift fire drills for the 3rd and 4th quarter of 2024. The drills were completed but records were initially missing and later located and sent to the Fire Marshal.”

Type AWAC §WAC 388-78A-2040
Verbatim citation text · WAC §WAC 388-78A-2040

“Facility failed to maintain fire safety per state fire marshal regulations. The facility failed three fire marshal inspections (07/26/2024, 09/25/2024, and 11/08/2024) and was out of compliance with multiple International Fire Code and WAC regulations, placing 30 residents, staff, and visitors at risk.”

Type AWAC §IFC 701.6 2021
Verbatim citation text · WAC §IFC 701.6 2021

“Facility failed to maintain annual inspection records of fire-resistance-rated construction and had holes found around piping in the fire alarm panel room. These holes were initially filled with non-rated material and later corrected with fire-retardant caulking.”

Type AWAC §IFC 705.2 2021
Verbatim citation text · WAC §IFC 705.2 2021

“Facility failed to provide annual fire door inspection reports and maintain fire doors properly. Fire doors throughout the building were found to have excessive gaps. Six doors could not be fixed by maintenance staff and were awaiting professional repair from a fire door specialist.”

Type AWAC §IFC 907.8 2021
Verbatim citation text · WAC §IFC 907.8 2021

“Fire alarm system maintenance records were deficient. The fire alarm panel breaker was missing a lock device, which was later ordered and installed.”

Type AWAC §IFC 1031.10.2 2021
Verbatim citation text · WAC §IFC 1031.10.2 2021

“Facility failed to provide records documenting annual testing of battery-powered emergency lighting equipment. Emergency lights were tested and found to have failed; batteries were subsequently replaced.”

Read raw inspector notes

WAC 388-78A-2040: Facility failed to maintain fire safety per state fire marshal regulations. The facility failed three fire marshal inspections (07/26/2024, 09/25/2024, and 11/08/2024) and was out of compliance with multiple International Fire Code and WAC regulations, placing 30 residents, staff, and visitors at risk. IFC 701.6 2021: Facility failed to maintain annual inspection records of fire-resistance-rated construction and had holes found around piping in the fire alarm panel room. These holes were initially filled with non-rated material and later corrected with fire-retardant caulking. IFC 705.2 2021: Facility failed to provide annual fire door inspection reports and maintain fire doors properly. Fire doors throughout the building were found to have excessive gaps. Six doors could not be fixed by maintenance staff and were awaiting professional repair from a fire door specialist. IFC 907.8 2021: Fire alarm system maintenance records were deficient. The fire alarm panel breaker was missing a lock device, which was later ordered and installed. IFC 1031.10.2 2021: Facility failed to provide records documenting annual testing of battery-powered emergency lighting equipment. Emergency lights were tested and found to have failed; batteries were subsequently replaced. WAC 212-12-044: Facility failed to provide records of night shift fire drills for the 3rd and 4th quarter of 2024. The drills were completed but records were initially missing and later located and sent to the Fire Marshal.

2024-04-01Annual Compliance VisitNo findings

Plain-language summary

A routine inspection was conducted in April 2024. The report does not provide specific findings, deficiencies, or compliance details in the available narrative. Families should contact DSHS directly or request the full inspection report for complete information about this facility's performance.

Source: Washington DSHS · Aging and Disability Services Administration. DSHS inspection portal →