Magnolia Place of Saxonburg: inspection reports
The PA DHS record for Magnolia Place of Saxonburg in Saxonburg, PA: every visit in the last three years, with each citation in the inspector’s own words. Back to the profile and its summaries.
7 visits, most recent first.
2026-06-02Annual Compliance VisitNo findings
Plain-language summary
This compliance visit is in the Pennsylvania Department of Human Services public file. No citation text was included for this visit.
2026-05-06Annual Compliance VisitNo findings
Plain-language summary
This compliance visit is in the Pennsylvania Department of Human Services public file. No citation text was included for this visit.
2026-01-06Annual Compliance Visit5 findings
Plain-language summary
On this compliance visit, the Pennsylvania Department of Human Services file includes this account: Resident #1's assessment did not address resident care needs and contained inaccurate information regarding ambulation ability, failing to meet assessment requirements.
“Resident #1's annual medical evaluation had a blank immunization area, failing to meet the requirement for complete annual medical evaluations.”
The home's plan of correction
On 02/03/26 PCHA educated LPN RSD and LPN Support Nurse on 2600.141(b)(1) regulatory requirements. Documentation will be maintained. By 02/06/26 LPN RSD will correct resident #1's DME. By 02/20/26 LPN RSD and LPN Support Nurse will complete an internal audit of all DMEs to measure overall compliance. Monthly internal audits of DMEs will continue for two additional months thereafter to ensure continued compliance. Documentation will be kept. Results of the internal audits will be reviewed by the PCHA during monthly QA meetings beginning 02/26/26. Documentation will be maintained.
“Resident #2's Ketoconazole cream administration on 1/6/26 at 6:00 p.m. was not initialed on the medication administration record. Additionally, prescribed medications for residents #2 and #3 on 12/16/25 were not administered but were falsely documented as administered by staff person A.”
The home's plan of correction
LPN Support Nurse immediately corrected medication administration record (MAR) of resident #2 after confirming with staff person medication was administered. By 02/20/26 all staff persons who administer medications will be re-educated by LPN RSD and LPN Support Nurse on 2600.187(b) regulatory requirements of recording medication at time of administration. Documentation will be kept. By 02/20/26 LPN RSD and LPN Support Nurse will complete an internal audit of medication administration records to measure overall compliance. Monthly internal audits of medication administration records will continue for two additional months thereafter to maintain continued compliance. Documentation shall be kept. Results of the internal audits will be reviewed by the PCHA during monthly QA meetings beginning 02/26/26. Documentation will be kept. On 12/16/25 LPN RSD immediately initiated medication error investigation related to resident #2 and resident #3 medication errors. Residents assessed for no adverse outcomes, physicians and responsible parties notified. LPN RSD and HR reviewed incident with staff person involved on 12/17/25. Responsible staff person terminated. PCHA educated all medication technicians on regulation 2600.187(b) and 2600.187(d) on 12/21/25 and 12/22/25 to prevent reoccurrence. Documentation will be kept. Beginning January 2026 LPN RSD, LPN Support Nurse and/or designee will interview five random residents per week for three months to measure ongoing compliance. Documentation will be kept. Results of resident interviews will be reviewed by the PCHA during monthly QA meetings beginning 02/26/26. Documentation will be kept.
“Multiple residents (#2, #3, #4) had prescribed medications that were not administered as directed by the prescriber on various dates (12/16/25 and 1/5/26), including Bumetanide, Metformin, Potassium Cl, Eliquis, Ketoconazole cream, and Mirtazapine.”
The home's plan of correction
On 12/16/25 LPN RSD immediately initiated medication error investigation upon notification related to resident #2 and resident #3 medication errors. Residents assessed for no adverse outcomes, physicians and responsible parties notified. LPN RSD and HR reviewed incident with staff person involved on 12/17/25. Responsible staff person terminated. LPN PCHA educated all medication technicians on regulation 2600.187(b) and 2600.187(d) on 12/21/25 and 12/22/25 to prevent reoccurrence. Documentation will be kept. Beginning January 2026 LPN RSD, LPN Support Nurse and/or designee will interview five random residents per week for three months to measure compliance with medication administration. Documentation will be kept. Results of resident interviews will be reviewed by the PCHA during monthly QA meetings beginning 02/26/26. Documentation will be kept. On 01/07/26 LPN Support Nurse later located Ketoconazole 2% cream for resident #2 during med cart audit with licensing representative. To prevent reoccurrence LPN Support Nurse will create designated area in medication carts for treatments by 02/20/26. Resident #4 Mirtazapine 15mg tablets delivered to the facility 1/6/26. PCHA, LPN RSD and LPN Support Nurse held a virtual meeting with pharmacy provider stakeholders on 2/5/26 to review medication delivery/availability to prevent reoccurrence. By 02/20/26 all staff persons who administer medications will be re-educated on 2600.187(d) regulatory requirements by LPN RSD and LPN Support Nurse. Documentation will be kept. By 02/20/26 LPN RSD and LPN PCHA will complete an internal audit of medication administration records to measure overall compliance. Monthly internal audits of medication administration records will continue for three additional months thereafter to ensure continued compliance. Documentation shall be kept. Results of the internal audits will be reviewed by the PCHA during monthly QA meetings beginning 02/26/26. Documentation will be kept.
“Resident #1's assessment did not address resident care needs and contained inaccurate information regarding ambulation ability, failing to meet assessment requirements.”
The home's plan of correction
On 02/03/26 PCHA educated LPN RSD and LPN Support Nurse on 2600.225(c) regulatory requirements. Documentation will be kept. By 02/06/26 LPN RSD an additional assessment will be completed for resident #1. By 02/20/26 LPN RSD and LPN Support Nurse will complete an internal audit of all resident assessments to measure overall compliance. Monthly internal audits of resident assessments will continue for two additional months thereafter to assure continued compliance. Results of the internal audits will be reviewed by the PCHA during monthly QA meetings beginning 02/26.26. Documentation will be kept.
“Resident #1's support plan was undated and did not indicate when the support plan was finalized, failing to meet the requirement for timely revision of support plans.”
The home's plan of correction
On 02/03/26 PCHA educated LPN RSD and LPN Support Nurse on regulatory requirements. Documentation will be kept.
2025-08-14Annual Compliance Visit1 finding
Plain-language summary
On this compliance visit, the Pennsylvania Department of Human Services file includes this account: A resident in the secure dementia care unit struck another resident in the head and legs, resulting in a red mark above the eye and scrapes on the legs. Staff had left the agitated resident alone in the shared room during incontinence care.
“A resident in the secure dementia care unit struck another resident in the head and legs, resulting in a red mark above the eye and scrapes on the legs. Staff had left the agitated resident alone in the shared room during incontinence care.”
The home's plan of correction
On 8/1/25 at 5:38 a.m. staff immediately moved Resident to safe area of SDCU and notified LPN PCHA. Staff instructed to maintain Resident in room as safety measure while notifying family and dispatching 911 for Resident transfer to ACMH ER for evaluation. Two onsite managers assisted in SDCU to maintain safe environment while LPN PCHA initiated 302 petition with Butler County Crisis Center for Community Resources for Resident. Staff instructed to notify spouse/POA Resident of incident and 302 petition. 302 warrant approved by 7:00 AM. Resident transferred to BMH ER with warrant upheld by 11:51 AM. Resident returned to facility with no new orders by 10:10 AM. Oral report to Butler County AAA PSS at 10:49 AM, written report submitted at 11:10 AM. Oral report to DHS Northwest Regional Office at 11:10 AM followed by Initial Incident Report submission at 7:05 PM. Resident seen by PCP and PBS Mental Health for follow-up with no new orders or negative outcomes. Resident deemed nursing facility clinically eligible. DCS will be educated on regulation 2600.42(b) by LPN PCHA and LPN RSD by September 26, 2025. Documentation will be kept. By 9/26/25 LPN PCHA and LPN RSD will conduct a behavioral status review of all SDCU Residents to ensure compliance with regulation 2600.42(b). Documentation will be kept. Beginning October 2025 audit results will be reviewed during the monthly QA/QI meeting.
2025-04-24Annual Compliance VisitNo findings
Plain-language summary
This compliance visit is in the Pennsylvania Department of Human Services public file. No citation text was included for this visit.
2025-01-15Annual Compliance Visit2 findings
Plain-language summary
On this compliance visit, the Pennsylvania Department of Human Services file includes this account: Fire drills conducted from January 2024 through December 2024 failed to use alternate exit routes, with all drills recording only "Safe Area" as the exit route used.
“Fire drill records did not include evacuation times in minutes and seconds for drills conducted on 11/26/24, 6/27/24, 4/30/24, and 1/29/24.”
The home's plan of correction
On 1/16/25 Maintenance Director educated by Administrator on regulation 2600.132(c) to include numerical seconds along with minutes when recording evacuation times as immediate corrective action. On 1/30/25 Fire Protection Engineer Atlantic Code Consultants reviewed regulation 2600.132(c) requirements conducted and observed a fire drill with Maintenance Director and Administrator to prevent reoccurrence. Beginning 1/30/25 Administrator and/or designee will audit fire drill records monthly for three months then quarterly for the remainder of 2025 to assure regulatory compliance. Documentation will be kept. Audits will be reviewed at monthly QA meetings beginning February 19, 2025.
“Fire drills conducted from January 2024 through December 2024 failed to use alternate exit routes, with all drills recording only "Safe Area" as the exit route used.”
The home's plan of correction
On 1/16/25 Maintenance Director educated by Administrator on regulation 2600.132(f) to include evacuation zones utilized when recording exit routes on the fire drill record as immediate corrective action. On 1/30/25 Fire Protection Engineer Atlantic Code Consultants reviewed regulation 2600.132(f) requirements conducted and observed a fire drill with Maintenance Director and Administrator to prevent reoccurrence. Beginning 1/30/25 Administrator and/or designee will audit fire drill records monthly for three months then quarterly for the remainder of 2025 to assure regulatory compliance. Documentation will be kept. Audits will be reviewed at monthly QA meetings beginning February 19, 2025.
2023-12-06Annual Compliance Visit8 findings
Plain-language summary
On this compliance visit, the Pennsylvania Department of Human Services file cites this requirement: Emergency evacuation diagrams must accurately show corridors, line of travel to exit doors, and location of fire extinguishers and pull signals.
“An uncovered/open garbage bag half filled with refuse was found in the kitchen located on the garden's unit. Trash in kitchens and bathrooms shall be kept in covered trash receptacles that prevent the penetration of insects and rodents.”
The home's plan of correction
On 12/06/23 facility maintenance director discarded garbage bag and placed a second trash receptacle in the kitchen to accommodate Styrofoam containers being utilized in response to a COVID-19 outbreak. Beginning 12/07/23 administrator will audit weekly for two months to ensure compliance. Documentation will be kept. Audits will be reviewed at monthly QA/QI meetings beginning January 2024. Current staff will be educated by administrator on regulation 2600.85(d) by 01/19/24.
“Resident #1 had no fitted sheets on bed. Each resident shall have clean and in good repair bed linens in the bedroom.”
The home's plan of correction
On 12/06/23 direct care staff applied a fitted sheet to the bed of resident #1. Beginning 12/07/23 administrator will audit beds throughout the facility on a weekly basis for two months to ensure compliance. Documentation will be kept. Audits will be reviewed at monthly QA/QI meetings beginning January 2024. Current staff will be educated by administrator on regulation 2600.101(j)(3) by 01/19/24.
“The common bathroom located next to the nurse station in the memory care unit had no toilet paper. Individual toiletry items including toothpaste, toothbrush, shampoo, deodorant, comb and hairbrush shall be made available to residents.”
The home's plan of correction
On 12/06/23 housekeeping staff replenished common bathroom toilet paper. Beginning 12/07/23 facility maintenance director and/or administrator will audit daily for two weeks then weekly for one month to ensure compliance. Housekeeping staff will audit daily thereafter. Documentation will be kept. Audits will be reviewed at monthly QA/QI meetings beginning January 2024. Current staff will be educated by administrator on regulation 2600.102(g) by 01/19/24.
“The fire safety diagram on the memory care unit indicated two sets of double fire safety doors present in the middle of the long hallway, but only one set of double fire safety doors is actually present. Emergency evacuation diagrams must accurately show corridors, line of travel to exit doors, and location of fire extinguishers and pull signals.”
The home's plan of correction
On 12/08/23 administrator located correct diagram and redisplayed. Diagram was accessed by contractor/vendor during active remodel project and inadvertently placed within picture frame. Administrator provided verbal education to contractors/vendors. Beginning 12/08/23 administrator will check diagram weekly for two months to assurance compliance. Documentation will be maintained and reviewed at QA/QI meetings beginning January 2024. On 11/29/23 facility maintenance director obtained a quote from SignPro to obtain permanent SDCU fire safety diagrams secondary to remodel project. Upon remodel project completion new fire safety diagrams will be installed to permanently prevent reoccurrence.
“The fire extinguisher next to the laundry room on the memory care unit had no attached documentation of an annual inspection conducted by a fire safety expert. Fire extinguishers shall be inspected and approved annually by a fire safety expert with the date of inspection on the extinguisher.”
The home's plan of correction
On 09/26/23 all fire extinguishers at the community were inspected by Fire Fighter Sales and Service Co. In addition to annual and semi annual inspections, the maintenance director inspects every fire extinguisher monthly in accordance with the criteria established in the National Fire protection Association Standard 10, Portable Fire Extinguishers. On 12/06/23 during the physical plant inspection one fire extinguisher with a damaged tag was observed. The extinguisher was inspected and dated to meet the criteria of NFPA 10. On 01/12/24 all fire extinguishers were inspected by Fire Fighter Sales and Service. Damaged tag replaced by fire safety expert. Resealable fire extinguisher tag covers were ordered and will be used in the SDCU preventively. Facility maintenance director will apply tag covers upon receipt in addition to retaining one inspected fire extinguisher on stock as emergency replacement measure. Fire safety expert will be verbally notified by facility maintenance director if tags become damaged and request replacement.
“The doorway in the rear of the memory care unit's dining room had signage indicating the egress as an exit, however, this point of egress was not an exit. Exit signs bearing the word 'EXIT' in plain legible letters shall be placed only at actual exits.”
The home's plan of correction
On 12/07/23 facility maintenance director removed exit sign. On 12/07/23 facility maintenance director installed permanent signage indicating no exit to outside of building from this courtyard. Beginning January 2024 facility maintenance director will audit signage monthly for three months to assure regulatory compliance.
“Resident #2 is prescribed insulin subcutaneously twice daily with instructions not to mix with other insulin, however the medication's label indicated inject 5 units subcutaneously twice a day without the complete instructions. Prescription medication labels shall include the prescribed dosage and instructions for administration.”
The home's plan of correction
On 12/06/23 a directions change label was applied to the original packaging for immediate correction. Resident services director and/or designee will complete entire house cart audit to measure compliance by 01/15/24. Current staff will be educated by resident services director and administrator on regulation 2600.184(a) by 01/19/24. Beginning 02/01/24 resident services director and/or designee will audit med carts monthly to ensure compliance. Documentation will be kept. Audits will be reviewed at monthly QA/QI meetings beginning January 2024.
“A medication administration record indicated a blood glucose level of 202 for Resident #2, however the resident's glucometer indicated a different blood glucose level at the previously specified date and time. The home shall develop and implement procedures for the safe storage, access, security, distribution and use of medications and medical equipment by trained staff persons.”
The home's plan of correction
Current staff will be educated by resident services director and administrator on regulation 2600.185(a).
Source: Pennsylvania Department of Human Services, Office of Long-Term Living. PA DHS inspection portal →