The DHSS record for Washington Place Memory Care in Washington, MO: every visit in the last three years, with each citation in the inspector’s own words. Back to the profile and its summaries.

Full record

5 visits, most recent first.

2025-01-28Complaint InvestigationNo findings

Plain-language summary

This complaint investigation is in the Missouri Department of Health and Senior Services public file. No citation text was included for this visit.

2025-01-16Annual Compliance Visit6 findings

Plain-language summary

A routine fire safety inspection on January 16, 2025 found three problems at this memory care facility: the fire alarm system had not received required semi-annual testing and maintenance, a kitchen door designed to close automatically to prevent smoke spread was being held open with a wedge (though it was closed during the inspection), and an emergency light near the furnace room did not work when tested. The facility has a plan to address each of these issues.

224919 CSR §2249
Verbatim citation text · 19 CSR §2249

“Based on record review and interview during a fire safety inspection, the facility failed to ensure the complete fire alarm system was tested and maintained in accordance with National Fire Protection Association (NFPA) 72, 1999 ed. The facility census was fifteen, this deficiency affects fifteen of fifteen residents. Record review revealed no semi-annual inspection had been performed on the fire alarm system. Semi-annual inspections are to be completed six (6) months after an annual inspection. During the exit interview on January 16, 2024 at 1340 the maintenance manager stated he believes the inspection has been conducted and would email me a copy. Followed-up at the facility on January 21, 2025 at 1145 to retrieve a copy of semi-annual fire alarm testing and inspection report. Opening the file revealed that it was an inspection report for a different facility. Contacted the alarm company and they advised they were not hired to do a semi-annual fire alarm inspection.”

225619 CSR §2256
Verbatim citation text · 19 CSR §2256

“Based on observation and interview during the fire safety inspection process, the facility failed to maintain self closing smoke partition doors that separate the kitchen area from the dining area. The facility census was fifteen, this deficiency affects fifteen of fifteen residents. Observation revealed the kitchen smoke partition door leading to the serving line was mechanically blocked open with a chock. This violation was corrected while on site. However, it is a reoccurring violation and requires a new plan of correction to prevent future occurrences. 6899 3J1511 COMPLETED 01/16/2025 PROVIDER'S PLAN OF CORRECTION (EACH CORRECTIVE ACTION SHOULD BE COMPLETE DATE 2701 RABBIT TRAIL DRIVE WASHINGTON, MO 63090 ARBORS VICT PL WASH, MEM CAR ASSTD LIVING Al During the exit interview on January 16, 2024 at 1310, maintenance stated he would see that the kitchen staff keeps the door closed.”

227819 CSR §2278
Verbatim citation text · 19 CSR §2278

“Based on observation and interview during the fire safety inspection process, the facility failed to ensure all emergency lighting was operational. The facility census was fifteen, this deficiency affects fifteen of fifteen residents. Observation revealed an emergency light that failed to illuminate while depressing the test button next to furnace room 10&11. During the exit interview on January 16, 2024 at 1315, maintenance stated it would be fixed.”

229819 CSR §2298
Verbatim citation text · 19 CSR §2298

“Based on observation and interview during the fire safety inspection process, the facility failed to store portable compressed gas cylinders in accordance with NFPA 99, 1999 Edition. The facility census was fifteen, this deficiency affects fifteen of fifteen residents.. Observation revealed 3 freestanding portable oxygen tanks not stored in an approved rack, or secured by chain or band in room 31. Further, there was no signage indicating the storage of oxygen in the room. During the exit interview on January 16, 2024 at 1320, maintenance stated he would make sure to have the compressed gas cylinders properly stored and the room appropriately labeled.”

320119 CSR §3201
Verbatim citation text · 19 CSR §3201

“Based on observation and interview during the fire safety inspection process, the facility failed to maintain the building in good repair. The facility census was fifteen, this deficiency affects fifteen of fifteen residents. Observation revealed a wall penetrations behind the faucets of the floor sink in the laundry room near room 29. 3J1511 COMPLETED 01/16/2025 PROVIDER'S PLAN OF CORRECTION (X5) (EACH CORRECTIVE ACTION SHOULD BE COMPLETE 01/16/2025 2701 RABBIT TRAIL DRIVE WASHINGTON, MO 63090 ARBORS VICT PL WASH, MEM CAR ASSTD LIVING Al These penetrations could allow smoke, fire, and gases to travel to unaffected portions of the building. During the exit interview on January 16, 2024 at 1325, maintenance stated he would would repair the holes in the drywall.”

321419 CSR §3214
Verbatim citation text · 19 CSR §3214

“Based on observation and interview during the 01/16/2025 2701 RABBIT TRAIL DRIVE WASHINGTON, MO 63090 ARBORS VICT PL WASH, MEM CAR ASSTD LIVING Al fire inspection process, the facility failed to ensure the facility's electric wiring was properly maintained. The facility census was fifteen, this deficiency affects fifteen of fifteen residents . Observation revealed an open junction box in the ceiling of the spa. Observation revealed an open junction box on the wall of furnace room 2. Observation revealed an open junction box behind the smoke partition door next to the salon. Observation revealed an open junction box behind the smoke partition door next to the storage room. Observation revealed a missing cover plate on the dryer outlet in the laundry. During the exit interview on January 16, 2024 at 1330, maintenance stated he would replace missing covers. PLAN OF CORRECTION Provider/Supplier Name: Arbors at VP Washington Citi 2701 Rabbit Trail Drive Washington MO 63090 Date of Survey: 1/16/2025 ID PREFIX TAG | PROVIDER'S PLAN OF CORRECTION: (EACH CORRECTIVE ACTION SHOULD BE CROSS-REFERENCED TO THE APPROPRIATE DEFICIENCY) 1. Set up semi-annual fire alarm inspection to be conducted. 2. Add semi annuai fire alarm inspection to current contract with provider. 2249- No 3. Keep inspection record log up to date to reflect semi- ; ‘ . nae . when semi annual fire alarm inspection is due. annual fire ,; ; . 4. Call provider for fire alarm inspection semi- alarm ; ; . annually by the end of the month prior to get inspection on schedule. Class Il 5. Completion date:1/28/2025 6. Completed by Maintenance Director and/or authorized representative. 2256 1. Hang sign notifying employees that the door Kitchen must always remain shut. door 2. Monitor door during work hours. blocked 3. Completion date: 1/28/2025 open Class 4. Completed by Director of Dining Services I and/or authorized representative. 1. Replace light in affected emergency light. 2. Check all emergency lights and replace any lights. 3. Complete monthly emergency light checks. 2278 Non ; functional 4. Complete annual emergency light checks. emeraenc 5. Replace any needed lights in emergency lights i hting y noticed during checks. Clase i 6. Completion date: 1/28/2025 7. Completed by Maintenance director and/or authorized representative. COMPLETION DATE 1/28/2025 1/28/2025 1/28/2025 ee . Move affected oxygen tanks to proper location and store properly until able to dispose of. 2. Check ail rooms in community to take 2298 ; inventory of oxygen tanks and proper storage. oon 3. Check oxygen tanks in community monthly for storage proper storage. Class III 4. Completion date:1/28/2025 5. Completed by Maintenance Director and/or authorized representative. . Patch holes in wall around affected faucets. 3201 Holes 2. Check all rooms for holes in walls around faucets and repair holes. in wall 3. Check all rooms monthly for holes in walls faucets around faucets and repair holes. Class Ill 4. Completion date: 1/28/2025 5. Completed by Maintenance Director and/or authorized representative. 1. Put cover plates on affected areas. 3214 2. Check all rooms for missing cover plates Missing and replace. electrical 3. Check all rooms monthly for cover plates cover and replace. plates 4. Completion date: 1/28/2025 Class III 5. Completed by Maintenance Director and/or authorized representative. 1/28/2025 1/28/2025 1/28/2025”

Read raw inspector notes

PRINTED: 01/23/2025 FORM APPROVED Missouri Department of Health and Senior Services STATEMENT OF DEFICIENCIES (X1) PROVIDER/SUPPLIER/CLIA {X2) MULTIPLE CONSTRUCTION (X3) DATE SURVEY AND PLAN OF CORRECTION IDENTIFICATION NUMBER: A. BUILDING: COMPLETED BWING 01/16/2025 NAME OF PROVIDER OR SUPPLIER STREET ADDRESS, CITY, STATE, ZiP CODE 2701 RABBIT TRAIL DRIVE WASHINGTON, MO 63090 (X4) ID SUMMARY STATEMENT OF DEFICIENCIES PROVIDER'S PLAN OF CORRECTION (x8) PREFIX (EACH DEFICIENCY MUST BE PRECEDED BY FULL (EACH CORRECTIVE ACTION SHOULD BE COMPLETE TAG REGULATORY OR LSC IDENTIFYING INFORMATION} CROSS-REFERENCED TO THE APPROPRIATE DATE DEFICIENCY) ARBORS VICT PL WASH, MEM CAR ASSTD LIVING Al A2249| 19 CSR 30-86.022(9)(C) Fire Alarm System-Test/Maintain Complete Fire Alarm Systems. (C) All facilities shall test and maintain the complete fire alarm system in accordance with NFPA 72, 1999 edition. [/Il This regulation is not met as evidenced by: Class II Based on record review and interview during a fire safety inspection, the facility failed to ensure the complete fire alarm system was tested and maintained in accordance with National Fire Protection Association (NFPA) 72, 1999 ed. The facility census was fifteen, this deficiency affects fifteen of fifteen residents. Record review revealed no semi-annual inspection had been performed on the fire alarm system. Semi-annual inspections are to be completed six (6) months after an annual inspection. During the exit interview on January 16, 2024 at 1340 the maintenance manager stated he believes the inspection has been conducted and would email me a copy. Followed-up at the facility on January 21, 2025 at 1145 to retrieve a copy of semi-annual fire alarm testing and inspection report. Opening the file revealed that it was an inspection report for a different facility. Contacted the alarm company and they advised they were not hired to do a semi-annual fire alarm inspection. 19 CSR 30-86.022(10)(A} Hazardous Area Requirements Missouri Department of Health and Senior Services A LABORATORY DIRECTOR'S OR PROVIDER/SUPPLIER REPRESENTATIVE'S SIGNATURE tme AdMunsrrvatok— — woypate 1/23 25 STATE FORM 6298 3J1511 lf continuation sheet 1 of 6 Missouri Department of Health and Senior Services STATEMENT OF DEFICIENCIES (X1) PROVIDER/SUPPLIER/CLIA AND PLAN OF CORRECTION IDENTIFICATION NUMBER: A. BUILDING: NAME OF PROVIDER OR SUPPLIER 2701 RABBIT TRAIL DRIVE ARBORS VICT PL WASH, MEM CAR ASSTD LIVING Al WASHINGTON, MO 63090 SUMMARY STATEMENT OF DEFICIENCIES (EACH DEFICIENCY MUST BE PRECEDED BY FULL REGULATORY OR LSC IDENTIFYING INFORMATION) (x4) ID PREFIX TAG Continued From page 1 Protection from Hazards. (A) In assisted living facilities and residential care facilities licensed on or after November 13, 1980, for more than twelve (12) beds, hazardous areas shall be separated by construction of at least a one- (1-) hour fire-resistant rating. In facilities equipped with a complete fire alarm system, the one- (1-) hour fire separation is required only for furnace or boiler rooms. Hazardous areas equipped with a complete sprinkler system are not required to have this one- (1-) hour fire separation. Doors to hazardous areas shall be self-closing and shall be kept closed unless an electromagnetic hold-open device is used which is interconnected with the fire alarm system. When the sprinkler option is chosen, the areas shall be separated from other spaces by smoke-resistant partitions and doors. The doors shall be self-closing or automatic-closing. Facilities formerly licensed as residential care facility | or Il, and existing prior to November 13, 1980, shall be exempt from this requirement. II This regulation is not met as evidenced by: Class II Based on observation and interview during the fire safety inspection process, the facility failed to maintain self closing smoke partition doors that separate the kitchen area from the dining area. The facility census was fifteen, this deficiency affects fifteen of fifteen residents. Observation revealed the kitchen smoke partition door leading to the serving line was mechanically blocked open with a chock. This violation was corrected while on site. However, it is a reoccurring violation and requires a new plan of correction to prevent future occurrences. Missouri Department of Health and Senior Services STATE FORM 6899 3J1511 (X2) MULTIPLE CONSTRUCTION PRINTED: 01/23/2025 FORM APPROVED (X3) DATE SURVEY COMPLETED 01/16/2025 STREET ADDRESS, CITY, STATE, ZIP CODE PROVIDER'S PLAN OF CORRECTION (EACH CORRECTIVE ACTION SHOULD BE CROSS-REFERENCED TO THE APPROPRIATE DEFICIENCY) (x5) COMPLETE DATE If continuation sheet 2 of 6 Missouri Department of Health and Senior Services STATEMENT OF DEFICIENCIES (X1) PROVIDER/SUPPLIER/CLIA AND PLAN OF CORRECTION IDENTIFICATION NUMBER: NAME OF PROVIDER OR SUPPLIER (X2) MULTIPLE CONSTRUCTION A. BUILDING: 2701 RABBIT TRAIL DRIVE WASHINGTON, MO 63090 ARBORS VICT PL WASH, MEM CAR ASSTD LIVING Al (X4) ID SUMMARY STATEMENT OF DEFICIENCIES PREFIX (EACH DEFICIENCY MUST BE PRECEDED BY FULL TAG REGULATORY OR LSC IDENTIFYING INFORMATION) Continued From page 2 During the exit interview on January 16, 2024 at 1310, maintenance stated he would see that the kitchen staff keeps the door closed. 19 CSR 30-86.022(12)(C) Emergency Lighting -Battery Powered, 1.5 hrs Emergency Lighting. (C) If battery-powered lights are used, they shall be capable of operating the light for at least one and one-half (1 1/2) hours. II This regulation is not met as evidenced by: Class II Based on observation and interview during the fire safety inspection process, the facility failed to ensure all emergency lighting was operational. The facility census was fifteen, this deficiency affects fifteen of fifteen residents. Observation revealed an emergency light that failed to illuminate while depressing the test button next to furnace room 10&11. During the exit interview on January 16, 2024 at 1315, maintenance stated it would be fixed. 19 CSR 30-86.022(17) Oxygen Storage Requirements Oxygen storage shall be in accordance with NFPA 99, 1999 Edition. II/III This regulation is not met as evidenced by: Class III Missouri Department of Health and Senior Services STATE FORM 6899 3J1511 PRINTED: 01/23/2025 FORM APPROVED (X3) DATE SURVEY COMPLETED 01/16/2025 STREET ADDRESS, CITY, STATE, ZIP CODE PROVIDER'S PLAN OF CORRECTION (X5) (EACH CORRECTIVE ACTION SHOULD BE COMPLETE CROSS-REFERENCED TO THE APPROPRIATE DATE DEFICIENCY) If continuation sheet 3 of 6 Missouri Department of Health and Senior Services STATEMENT OF DEFICIENCIES (X1) PROVIDER/SUPPLIER/CLIA AND PLAN OF CORRECTION IDENTIFICATION NUMBER: NAME OF PROVIDER OR SUPPLIER (X2) MULTIPLE CONSTRUCTION A. BUILDING: 2701 RABBIT TRAIL DRIVE WASHINGTON, MO 63090 ARBORS VICT PL WASH, MEM CAR ASSTD LIVING Al (X4) ID SUMMARY STATEMENT OF DEFICIENCIES PREFIX (EACH DEFICIENCY MUST BE PRECEDED BY FULL TAG REGULATORY OR LSC IDENTIFYING INFORMATION) Continued From page 3 Based on observation and interview during the fire safety inspection process, the facility failed to store portable compressed gas cylinders in accordance with NFPA 99, 1999 Edition. The facility census was fifteen, this deficiency affects fifteen of fifteen residents.. Observation revealed 3 freestanding portable oxygen tanks not stored in an approved rack, or secured by chain or band in room 31. Further, there was no signage indicating the storage of oxygen in the room. During the exit interview on January 16, 2024 at 1320, maintenance stated he would make sure to have the compressed gas cylinders properly stored and the room appropriately labeled. 19 CSR 30-86.032(2) Substantially Constructed & A3201 Maintained The building shall be substantially constructed and shall be maintained in good repair and in accordance with the construction and fire safety rules in effect at the time of initial licensing. II/III This regulation is not met as evidenced by: Class III Based on observation and interview during the fire safety inspection process, the facility failed to maintain the building in good repair. The facility census was fifteen, this deficiency affects fifteen of fifteen residents. Observation revealed a wall penetrations behind the faucets of the floor sink in the laundry room near room 29. Missouri Department of Health and Senior Services STATE FORM 6899 3J1511 PRINTED: 01/23/2025 FORM APPROVED (X3) DATE SURVEY COMPLETED 01/16/2025 STREET ADDRESS, CITY, STATE, ZIP CODE PROVIDER'S PLAN OF CORRECTION (X5) (EACH CORRECTIVE ACTION SHOULD BE COMPLETE CROSS-REFERENCED TO THE APPROPRIATE DATE DEFICIENCY) If continuation sheet 4 of 6 PRINTED: 01/23/2025 FORM APPROVED Missouri Department of Health and Senior Services STATEMENT OF DEFICIENCIES (X1) PROVIDER/SUPPLIER/CLIA (X2) MULTIPLE CONSTRUCTION (X3) DATE SURVEY AND PLAN OF CORRECTION IDENTIFICATION NUMBER: A. BUILDING: COMPLETED 01/16/2025 NAME OF PROVIDER OR SUPPLIER STREET ADDRESS, CITY, STATE, ZIP CODE 2701 RABBIT TRAIL DRIVE WASHINGTON, MO 63090 (X4) ID SUMMARY STATEMENT OF DEFICIENCIES PROVIDER'S PLAN OF CORRECTION (X5) PREFIX (EACH DEFICIENCY MUST BE PRECEDED BY FULL (EACH CORRECTIVE ACTION SHOULD BE COMPLETE TAG REGULATORY OR LSC IDENTIFYING INFORMATION) CROSS-REFERENCED TO THE APPROPRIATE DATE DEFICIENCY) ARBORS VICT PL WASH, MEM CAR ASSTD LIVING Al Continued From page 4 These penetrations could allow smoke, fire, and gases to travel to unaffected portions of the building. During the exit interview on January 16, 2024 at 1325, maintenance stated he would would repair the holes in the drywall. 19 CSR 30-86.032(13) Electrical Wiring, Maintained, Inspected In facilities that are constructed or have plans approved after July 1, 2005, electrical wiring shall be installed and maintained in accordance with the requirements of the National Electrical Code, 1999 edition, National Fire Protection Association, Inc., incorporated by reference, in this rule and available by mail at One Batterymarch Park, Quincy, MA 02269, and local codes. This rule does not incorporate any subsequent amendments or additions to the materials incorporated by reference. Facilities built between September 28, 1979 and July 1, 2005 shall be maintained in accordance with the requirements of the National Electrical Code, which was in effect at the time of the original plan approval and local codes. This rule does not incorporate any subsequent amendments or additions. In facilities built prior to September 28, 1979, electrical wiring shall be maintained in good repair and shall not present a safety hazard. All facilities shall have wiring inspected every two (2) years by a qualified electrician. II/III This regulation is not met as evidenced by: Class III Based on observation and interview during the Missouri Department of Health and Senior Services STATE FORM 6899 3J1511 If continuation sheet 5 of 6 PRINTED: 01/23/2025 FORM APPROVED Missouri Department of Health and Senior Services STATEMENT OF DEFICIENCIES (X1) PROVIDER/SUPPLIER/CLIA (X2) MULTIPLE CONSTRUCTION (X3) DATE SURVEY AND PLAN OF CORRECTION IDENTIFICATION NUMBER: A. BUILDING: COMPLETED 01/16/2025 NAME OF PROVIDER OR SUPPLIER STREET ADDRESS, CITY, STATE, ZIP CODE 2701 RABBIT TRAIL DRIVE WASHINGTON, MO 63090 (X4) ID SUMMARY STATEMENT OF DEFICIENCIES PROVIDER'S PLAN OF CORRECTION (X5) PREFIX (EACH DEFICIENCY MUST BE PRECEDED BY FULL (EACH CORRECTIVE ACTION SHOULD BE COMPLETE TAG REGULATORY OR LSC IDENTIFYING INFORMATION) CROSS-REFERENCED TO THE APPROPRIATE DATE DEFICIENCY) ARBORS VICT PL WASH, MEM CAR ASSTD LIVING Al Continued From page 5 fire inspection process, the facility failed to ensure the facility's electric wiring was properly maintained. The facility census was fifteen, this deficiency affects fifteen of fifteen residents . Observation revealed an open junction box in the ceiling of the spa. Observation revealed an open junction box on the wall of furnace room 2. Observation revealed an open junction box behind the smoke partition door next to the salon. Observation revealed an open junction box behind the smoke partition door next to the storage room. Observation revealed a missing cover plate on the dryer outlet in the laundry. During the exit interview on January 16, 2024 at 1330, maintenance stated he would replace missing covers. Missouri Department of Health and Senior Services STATE FORM 6899 3J1511 If continuation sheet 6 of 6 PLAN OF CORRECTION Provider/Supplier Name: Arbors at VP Washington Citi 2701 Rabbit Trail Drive Washington MO 63090 Date of Survey: 1/16/2025 ID PREFIX TAG | PROVIDER'S PLAN OF CORRECTION: (EACH CORRECTIVE ACTION SHOULD BE CROSS-REFERENCED TO THE APPROPRIATE DEFICIENCY) 1. Set up semi-annual fire alarm inspection to be conducted. 2. Add semi annuai fire alarm inspection to current contract with provider. 2249- No 3. Keep inspection record log up to date to reflect semi- ; ‘ . nae . when semi annual fire alarm inspection is due. annual fire ,; ; . 4. Call provider for fire alarm inspection semi- alarm ; ; . annually by the end of the month prior to get inspection on schedule. Class Il 5. Completion date:1/28/2025 6. Completed by Maintenance Director and/or authorized representative. 2256 1. Hang sign notifying employees that the door Kitchen must always remain shut. door 2. Monitor door during work hours. blocked 3. Completion date: 1/28/2025 open Class 4. Completed by Director of Dining Services I and/or authorized representative. 1. Replace light in affected emergency light. 2. Check all emergency lights and replace any lights. 3. Complete monthly emergency light checks. 2278 Non ; functional 4. Complete annual emergency light checks. emeraenc 5. Replace any needed lights in emergency lights i hting y noticed during checks. Clase i 6. Completion date: 1/28/2025 7. Completed by Maintenance director and/or authorized representative. COMPLETION DATE 1/28/2025 1/28/2025 1/28/2025 ee . Move affected oxygen tanks to proper location and store properly until able to dispose of. 2. Check ail rooms in community to take 2298 ; inventory of oxygen tanks and proper storage. oon 3. Check oxygen tanks in community monthly for storage proper storage. Class III 4. Completion date:1/28/2025 5. Completed by Maintenance Director and/or authorized representative. . Patch holes in wall around affected faucets. 3201 Holes 2. Check all rooms for holes in walls around faucets and repair holes. in wall 3. Check all rooms monthly for holes in walls faucets around faucets and repair holes. Class Ill 4. Completion date: 1/28/2025 5. Completed by Maintenance Director and/or authorized representative. 1. Put cover plates on affected areas. 3214 2. Check all rooms for missing cover plates Missing and replace. electrical 3. Check all rooms monthly for cover plates cover and replace. plates 4. Completion date: 1/28/2025 Class III 5. Completed by Maintenance Director and/or authorized representative. 1/28/2025 1/28/2025 1/28/2025

2024-11-20Annual Compliance VisitNo findings

Plain-language summary

This routine visit is in the Missouri Department of Health and Senior Services public file. No citation text was included for this visit.

2024-03-05Annual Compliance VisitNo findings

Plain-language summary

This routine visit is in the Missouri Department of Health and Senior Services public file. No citation text was included for this visit.

2023-11-30Complaint Investigation2 findings

Plain-language summary

On this complaint investigation, the Missouri Department of Health and Senior Services file cites this requirement: The administrator shall develop and implement a safe and effective system of medication control and use, which assures that all residents ' medications are administered by personnel at least eighteen (18) years of age, in accordance.

479719 CSR §4797
Regulation cited · 19 CSR §4797

“The administrator shall develop and implement a safe and effective system of medication control and use, which assures that all residents ' medications are administered by personnel at least eighteen (18) years of age, in accordance with physicians ' instructions using acceptable nursing techniques. The facility shall employ a licensed nurse eight (8) hours per week for every thirty (30) residents to monitor each resident ' s condition and medication. Administration of medication shall mean delivering to a resident his or her prescription medication either in the original pharmacy container, or for internal medication, removing an individual dose from the pharmacy container and placing it in a small cup container or liquid medium for the resident to remove from the container and self-administer. External prescription medication may be applied by facility personnel if the resident is unable to do so and the resident ' s physician so authorizes. All individuals who administer medication shall be trained in medication administration and, if not a physician or a licensed nurse, shall be a certified medication technician or level I medication aide. I/II”

This is the rule that was cited, not the inspector’s specific finding.

Complaint19 CSR §4505
Regulation cited · 19 CSR §4505

“General Requirements. (A) If the facility admits or retains any individual needing more than minimal assistance due to having a physical, cognitive or other impairment that prevents the individual from safely evacuating the facility, the facility shall: 5. Include an individualized evacuation plan in the resident ' s individual service plan; II”

This is the rule that was cited, not the inspector’s specific finding.

Source: Missouri Dept. of Health and Senior Services · Section for Long-Term Care Regulation. DHSS inspection portal →