Crab Apple Village Senior Estates: inspection reports
The DHSS record for Crab Apple Village Senior Estates in Saint Clair, MO: every visit in the last three years, with each citation in the inspector’s own words. Back to the profile and its summaries.
4 visits, most recent first.
2025-10-07Annual Compliance Visit5 findings
Plain-language summary
During a routine fire safety inspection on October 7, 2025, inspectors found three violations: the basement rear exit corridor was blocked with beds, furniture, and assistive devices; the facility had no annual fire alarm system inspection records for 2025; and a kitchen serving window door that should have been self-closing was not functioning properly. The facility did not submit a plan to correct these violations by the deadline, so no corrective actions are documented.
“Based on an observation and interview during the fire safety inspection process on October 7, 2025, the facility failed to maintain their exit corridors free of obstructions. The facility census was sixty (60). This deficiency affected sixty (60) of sixty (60) residents. Observation on October 7, 2025 at 2:45 PM revealed the basement rear exit corridor partially obstructed with beds, furniture, and assistive devices. During the exit interview on October 7, 2025 at 3:25 PM, the DON advised she would have staff clear the hallway.”
“Based on record review and interview during a COMPLETED 10/07/2025 214 HARTMAN PLACE, SUITE 100 CRAB APPLE VILLAGE SENIOR ESTATES SAINT CLAIR, MO 63077 TAG fire safety inspection process on October 7, 2025, the facility failed to ensure the complete fire alarm system was tested and maintained in accordance with National Fire Protection Association (NFPA) 72, 1999 ed.. The facility census was sixty (60). This deficiency affected sixty (60) of sixty (60) residents. Record review on October 7, 2025 at 3:10 PM, revealed no annual or semi annual fire inspection reports for the fire alarm system for 2025. During the exit interview on October 7, 2025 at 3:30 PM , the DON called the administrator. | spoke with her and she stated she was out of town, but would return on October 8, 2025 and email the reports to me. Follow up on October 8, 2025 at 8:00 PM, no reports were received by the close of business today.”
“Based on observation and interview during the fire safety inspection process on October 7, 2025, the facility failed to properly maintain a self-closing smoke partition door to hazardous areas that separate them from the residential spaces. The facility census was sixty (60). This deficiency affected sixty (60) of sixty (60) residents. Observation on October 7, 2025 at 1:35 PM, revealed that the kitchen serving window was 2 shutter style doors that are not self-closing, nor attached to the fire alarm, and are not suitable smoke partitions. Observation on October 7, 2025 at 3:20 PM, revealed staff had blocked open the first floor laundry door. The door had been closed earlier in the inspection. During the exit interview on October 7, 2025 at 3:40 PM , the DON advised she would pass along to the owners.”
“Based on observation and interview during the fire safety inspection process on October 7, 2025, the facility, licensed after December 31, 1987 for more than twenty (20) beds, failed to ensure doors in a smoke partition closed completely. The facility census was sixty (60). This deficiency affected sixty (60) of sixty (60) residents. Observation on October 7, 2025 at 2:20 PM, revealed that the smoke partition doors next to room 210 failed to close completely on any of three (3) attempts. Smoke doors failing to close completely could allow smoke and toxic gases to spread to unaffected areas of the building. During the exit interview on October 7, 2025 at 3:45 PM , the DON advised she would notify the owners. 6899 X0S611 COMPLETED 10/07/2025 214 HARTMAN PLACE, SUITE 100 PROVIDER'S PLAN OF CORRECTION (EACH CORRECTIVE ACTION SHOULD BE COMPLETE DATE 214 HARTMAN PLACE, SUITE 100 SAINT CLAIR, MO 63077 CRAB APPLE VILLAGE SENIOR ESTATES TAG”
“Based on record review and interview during the fire safety inspection process on October 7, 2025, the facility failed to inspect and maintain the sprinkler system in accordance with NFPA 25, 1998 edition. The facility census was sixty (60). This deficiency affected sixty (60) of sixty (60) residents. Record review on October 7, 2025 at 3:15 PM, revealed no current annual fire sprinkler inspection report. During the exit interview on October 7, 2025 at 3:30 PM , the DON called the administrator. | spoke with her and she stated she was out of town, but would return on October 8, 2025 and email the reports to me. Follow up on October 8, 2025 at 8:00 PM, no reports were received by the close of business today. 6899 X0S611 COMPLETED 10/07/2025 PROVIDER'S PLAN OF CORRECTION (EACH CORRECTIVE ACTION SHOULD BE COMPLETE DATE”
Read raw inspector notesClose inspector notes
THE FACILITY DID NOT RETURN A PLAN OF CORRECTION THEREFORE, NO POC IS INCLUDED WITH THE STATEMENT OF DEFICIENCIES (2567 FORM) PRINTED: 02/09/2026 FORM APPROVED Missouri Department of Health and Senior Services STATEMENT OF DEFICIENCIES (X1) PROVIDER/SUPPLIER/CLIA (X2) MULTIPLE CONSTRUCTION (X3) DATE SURVEY AND PLAN OF CORRECTION IDENTIFICATION NUMBER: A. BUILDING: COMPLETED 10/07/2025 NAME OF PROVIDER OR SUPPLIER STREET ADDRESS, CITY, STATE, ZIP CODE 214 HARTMAN PLACE, SUITE 100 SAINT CLAIR, MO 63077 (X4) ID SUMMARY STATEMENT OF DEFICIENCIES PROVIDER'S PLAN OF CORRECTION (X5) PREFIX (EACH DEFICIENCY MUST BE PRECEDED BY FULL (EACH CORRECTIVE ACTION SHOULD BE COMPLETE TAG REGULATORY OR LSC IDENTIFYING INFORMATION) CROSS-REFERENCED TO THE APPROPRIATE DATE DEFICIENCY) CRAB APPLE VILLAGE SENIOR ESTATES 19 CSR 30-86.022(7)(G) Stairways/Corridors Free of Obstructions Exits, Stairways, and Fire Escapes. (G) All stairways and corridors shall be easily negotiable and shall be maintained free of obstructions. II This regulation is not met as evidenced by: Class II Based on an observation and interview during the fire safety inspection process on October 7, 2025, the facility failed to maintain their exit corridors free of obstructions. The facility census was sixty (60). This deficiency affected sixty (60) of sixty (60) residents. Observation on October 7, 2025 at 2:45 PM revealed the basement rear exit corridor partially obstructed with beds, furniture, and assistive devices. During the exit interview on October 7, 2025 at 3:25 PM, the DON advised she would have staff clear the hallway. 19 CSR 30-86.022(9)(D) Fire Alarm System Inspections/Certifications Complete Fire Alarm Systems. (D) All facilities shall have inspections and written certifications of the complete fire alarm system completed by an approved qualified service representative in accordance with NFPA 72, 1999 edition, at least annually. I/II This regulation is not met as evidenced by: Class II Based on record review and interview during a Missouri Department of Health and Senior Services LABORATORY DIRECTOR'S OR PROVIDER/SUPPLIER REPRESENTATIVE'S SIGNATURE TITLE (X6) DATE STATE FORM 6899 x0S611 If continuation sheet 1 of 5 Missouri Department of Health and Senior Services STATEMENT OF DEFICIENCIES (X1) PROVIDER/SUPPLIER/CLIA AND PLAN OF CORRECTION IDENTIFICATION NUMBER: A. BUILDING: NAME OF PROVIDER OR SUPPLIER (X2) MULTIPLE CONSTRUCTION PRINTED: 02/09/2026 FORM APPROVED (X3) DATE SURVEY COMPLETED 10/07/2025 STREET ADDRESS, CITY, STATE, ZIP CODE 214 HARTMAN PLACE, SUITE 100 CRAB APPLE VILLAGE SENIOR ESTATES SAINT CLAIR, MO 63077 SUMMARY STATEMENT OF DEFICIENCIES (EACH DEFICIENCY MUST BE PRECEDED BY FULL REGULATORY OR LSC IDENTIFYING INFORMATION) (x4) ID PREFIX TAG Continued From page 1 fire safety inspection process on October 7, 2025, the facility failed to ensure the complete fire alarm system was tested and maintained in accordance with National Fire Protection Association (NFPA) 72, 1999 ed.. The facility census was sixty (60). This deficiency affected sixty (60) of sixty (60) residents. Record review on October 7, 2025 at 3:10 PM, revealed no annual or semi annual fire inspection reports for the fire alarm system for 2025. During the exit interview on October 7, 2025 at 3:30 PM , the DON called the administrator. | spoke with her and she stated she was out of town, but would return on October 8, 2025 and email the reports to me. Follow up on October 8, 2025 at 8:00 PM, no reports were received by the close of business today. 19 CSR 30-86.022(10)(A) Hazardous Area Requirements Protection from Hazards. (A) In assisted living facilities and residential care facilities licensed on or after November 13, 1980, for more than twelve (12) beds, hazardous areas shall be separated by construction of at least a one- (1-) hour fire-resistant rating. In facilities equipped with a complete fire alarm system, the one- (1-) hour fire separation is required only for furnace or boiler rooms. Hazardous areas equipped with a complete sprinkler system are not required to have this one- (1-) hour fire separation. Doors to hazardous areas shall be self-closing and shall be kept closed unless an electromagnetic hold-open device is used which Missouri Department of Health and Senior Services STATE FORM 6899 X0S611 PROVIDER'S PLAN OF CORRECTION (EACH CORRECTIVE ACTION SHOULD BE CROSS-REFERENCED TO THE APPROPRIATE DEFICIENCY) (x5) COMPLETE DATE If continuation sheet 2 of 5 Missouri Department of Health and Senior Services STATEMENT OF DEFICIENCIES (X1) PROVIDER/SUPPLIER/CLIA AND PLAN OF CORRECTION IDENTIFICATION NUMBER: A. BUILDING: NAME OF PROVIDER OR SUPPLIER (X2) MULTIPLE CONSTRUCTION PRINTED: 02/09/2026 FORM APPROVED (X3) DATE SURVEY COMPLETED 10/07/2025 STREET ADDRESS, CITY, STATE, ZIP CODE 214 HARTMAN PLACE, SUITE 100 CRAB APPLE VILLAGE SENIOR ESTATES SAINT CLAIR, MO 63077 SUMMARY STATEMENT OF DEFICIENCIES (EACH DEFICIENCY MUST BE PRECEDED BY FULL REGULATORY OR LSC IDENTIFYING INFORMATION) (x4) ID PREFIX TAG Continued From page 2 is interconnected with the fire alarm system. When the sprinkler option is chosen, the areas shall be separated from other spaces by smoke-resistant partitions and doors. The doors shall be self-closing or automatic-closing. Facilities formerly licensed as residential care facility | or Il, and existing prior to November 13, 1980, shall be exempt from this requirement. II This regulation is not met as evidenced by: Class II Based on observation and interview during the fire safety inspection process on October 7, 2025, the facility failed to properly maintain a self-closing smoke partition door to hazardous areas that separate them from the residential spaces. The facility census was sixty (60). This deficiency affected sixty (60) of sixty (60) residents. Observation on October 7, 2025 at 1:35 PM, revealed that the kitchen serving window was 2 shutter style doors that are not self-closing, nor attached to the fire alarm, and are not suitable smoke partitions. Observation on October 7, 2025 at 3:20 PM, revealed staff had blocked open the first floor laundry door. The door had been closed earlier in the inspection. During the exit interview on October 7, 2025 at 3:40 PM , the DON advised she would pass along to the owners. 19 CSR 30-86.022(10)(1) Smoke Section Partitions > than 20 beds Missouri Department of Health and Senior Services STATE FORM 6899 X0S611 PROVIDER'S PLAN OF CORRECTION (EACH CORRECTIVE ACTION SHOULD BE CROSS-REFERENCED TO THE APPROPRIATE DEFICIENCY) (x5) COMPLETE DATE If continuation sheet 3 of 5 Missouri Department of Health and Senior Services STATEMENT OF DEFICIENCIES (X1) PROVIDER/SUPPLIER/CLIA AND PLAN OF CORRECTION IDENTIFICATION NUMBER: A. BUILDING: NAME OF PROVIDER OR SUPPLIER CRAB APPLE VILLAGE SENIOR ESTATES SAINT CLAIR, MO 63077 SUMMARY STATEMENT OF DEFICIENCIES (EACH DEFICIENCY MUST BE PRECEDED BY FULL REGULATORY OR LSC IDENTIFYING INFORMATION) (x4) ID PREFIX TAG Continued From page 3 Protection from Hazards. (I) In facilities whose plans were approved or which were initially licensed after December 31, 1987, for more than twenty (20) beds and all facilities licensed after August 28, 2007, each smoke section shall be separated by one- (1-) hour fire-rated smoke partitions. The smoke partitions shall be continuous from outside wall-to-outside wall and from floor-to-floor or floor-to-roof deck. All doors in this wall shall be at least twenty- (20-) minute fire-rated or its equivalent, self-closing, and may be held open only if the door closes automatically upon activation of the complete fire alarm system. II This regulation is not met as evidenced by: Class II Based on observation and interview during the fire safety inspection process on October 7, 2025, the facility, licensed after December 31, 1987 for more than twenty (20) beds, failed to ensure doors in a smoke partition closed completely. The facility census was sixty (60). This deficiency affected sixty (60) of sixty (60) residents. Observation on October 7, 2025 at 2:20 PM, revealed that the smoke partition doors next to room 210 failed to close completely on any of three (3) attempts. Smoke doors failing to close completely could allow smoke and toxic gases to spread to unaffected areas of the building. During the exit interview on October 7, 2025 at 3:45 PM , the DON advised she would notify the owners. Missouri Department of Health and Senior Services STATE FORM 6899 X0S611 (X2) MULTIPLE CONSTRUCTION PRINTED: 02/09/2026 FORM APPROVED (X3) DATE SURVEY COMPLETED 10/07/2025 STREET ADDRESS, CITY, STATE, ZIP CODE 214 HARTMAN PLACE, SUITE 100 PROVIDER'S PLAN OF CORRECTION (EACH CORRECTIVE ACTION SHOULD BE CROSS-REFERENCED TO THE APPROPRIATE DEFICIENCY) (x5) COMPLETE DATE If continuation sheet 4 of 5 Missouri Department of Health and Senior Services STATEMENT OF DEFICIENCIES (X1) PROVIDER/SUPPLIER/CLIA AND PLAN OF CORRECTION IDENTIFICATION NUMBER: A. BUILDING: NAME OF PROVIDER OR SUPPLIER 214 HARTMAN PLACE, SUITE 100 SAINT CLAIR, MO 63077 CRAB APPLE VILLAGE SENIOR ESTATES SUMMARY STATEMENT OF DEFICIENCIES (EACH DEFICIENCY MUST BE PRECEDED BY FULL REGULATORY OR LSC IDENTIFYING INFORMATION) (x4) ID PREFIX TAG Continued From page 4 19 CSR 30-86.022(11)(F) Sprinkler Systems-Inspections, Cert. Sprinkler Systems. (F) All facilities shall have inspections and written certifications of the approved sprinkler system completed by an approved qualified service representative in accordance with NFPA 25, 1998 edition. The inspections shall be in accordance with the provisions of NFPA 25, 1998 edition, with certification at least annually by a qualified service representative. 1/Il This regulation is not met as evidenced by: Class II Based on record review and interview during the fire safety inspection process on October 7, 2025, the facility failed to inspect and maintain the sprinkler system in accordance with NFPA 25, 1998 edition. The facility census was sixty (60). This deficiency affected sixty (60) of sixty (60) residents. Record review on October 7, 2025 at 3:15 PM, revealed no current annual fire sprinkler inspection report. During the exit interview on October 7, 2025 at 3:30 PM , the DON called the administrator. | spoke with her and she stated she was out of town, but would return on October 8, 2025 and email the reports to me. Follow up on October 8, 2025 at 8:00 PM, no reports were received by the close of business today. Missouri Department of Health and Senior Services STATE FORM 6899 X0S611 (X2) MULTIPLE CONSTRUCTION CROSS-REFERENCED TO THE APPROPRIATE PRINTED: 02/09/2026 FORM APPROVED (X3) DATE SURVEY COMPLETED 10/07/2025 STREET ADDRESS, CITY, STATE, ZIP CODE PROVIDER'S PLAN OF CORRECTION (EACH CORRECTIVE ACTION SHOULD BE (x5) COMPLETE DATE DEFICIENCY) If continuation sheet 5 of 5
2025-02-20Complaint Investigation2 findings
Plain-language summary
On this complaint investigation, the Missouri Department of Health and Senior Services file cites this requirement: The facility shall develop and implement written policies and procedures that prohibit mistreatment, neglect, and abuse of any resident and misappropriation of resident property and funds, and develop and implement policies that require.
“The facility shall develop and implement written policies and procedures that prohibit mistreatment, neglect, and abuse of any resident and misappropriation of resident property and funds, and develop and implement policies that require a report to be made to the department for any resident or to both the department and the Department of Mental Health for any vulnerable person whom the administrator or employee has reasonable cause to believe has been abused or neglected. II/III”
This is the rule that was cited, not the inspector’s specific finding.
“In case of behaviors that present a reasonable likelihood of serious harm to himself or herself or others, serious illness, significant change in condition, injury or death, staff shall take appropriate action and shall promptly attempt to contact the person listed in the resident ' s record as the legally authorized representative, designee or placement authority. The facility shall contact the attending physician or designee and notify the local coroner or medical examiner immediately upon the death of any resident of the facility prior to transferring the deceased resident to a funeral home. I/II”
This is the rule that was cited, not the inspector’s specific finding.
2024-10-04Annual Compliance VisitNo findings
Plain-language summary
This routine visit is in the Missouri Department of Health and Senior Services public file. No citation text was included for this visit.
2024-10-03Annual Compliance Visit6 findings
Plain-language summary
During a routine fire safety inspection on October 3, 2024, inspectors found three violations affecting all 62 residents: a basement exit door that required excessive force to open, an exit sign in the dining room that only illuminated briefly before failing, and several doors to hazardous areas (laundry, kitchen) that were not properly closing or lacked self-closing devices as required. The facility manager acknowledged these issues during the inspection and indicated willingness to make repairs.
“Based on observation and interview during the fire safety inspection process, the facility failed to maintain unobstructed exits remote from each other. The facility census was sixty-two. This deficiency affected sixty-two of sixty-two residents. Observation revealed the exit door beyond the basement laundry is sticking, excessive force was required to open the door. During the exit interview on October 3, 2024 at 0930, the manager stated that they preferred the door be hard to open, due to it being in Memory Care, but would repair it if needed.”
“Based on observation and interview during the fire safety inspection process, the facility failed to ensure all exit signs were operational, The facility census was sixty-two. This deficiency affected ment of Health and Senior Services Missouri Dapg EG9SR11 If coniInuatibn s bel 10f6 CRAB APPLE VILLAGE SENIOR ESTATES SAINT CLAIR, MO 63077 TAG | sixty-two of sixty-two residents. Observation revealed an exit sign/emergency light that would illuminate while depressing the test button, but only for a couple of seconds before it failed, in the dining room. During the exit interview on October 3, 2024 at 0935, the manager stated she would have the exit sign repaired,”
“Based on observation and interview during the fire safety inspection process on November 15, 2023 the facility failed to properly maintain a self-closing smoke partition door to hazardous areas that separate them from the residential spaces. The facility census was sixty-two. This deficiency affected sixty-two of sixty-two residents. Observation revealed the self-closure devices on the laundry room smoke partition doors were not adjusted properly to close the doors. Observation revealed the self-closure device on the kitchen scullery smoke partition door was not properly adjusted to close the door Observation revealed no self-closure device on the main kitchen smoke partition.door. Observation reveled the kitchen window was 2 shutter style doors that were not self-closing, nor attached to the fire alarm, and are not smoke partitions. During the exit interview on October 3, 2024 at 0940, the manager stated that the window was approved in plan review and has always been this way. She stated she would have maintenance adjust the doors on all the faundry rooms and kitchen, plus install a self-closure device on the other kitchen door.”
“Based on observation and interview during the fire safety inspection process, the facility, licensed after December 31, 1987 for more than twenty (20) beds, failed to ensure doors in a smoke partition closed completely. The facility census was sixty-two. This deficiency affected sixty-two of sixty-two residents. Observation of a smoke door next to room 308 revealed that the smoke doors missing the trim, leaving a noticeable gap between the doors. Smoke doors failing to close completely will allow smoke and toxic gases to spread to other areas of the building. During the exit interview on October 3, 2024 at 0945, the manager stated that they would have the door repaired.”
“Based on observation and interview during the fire safety inspection process, the facility failed to maintain a complete sprinkler system in accordance with NFPA 13, 1999 edition. The facility census was sixty-two. This deficiency affected sixty-two of sixty-two residents. Observation revealed a missing escutcheon ring in roam 115. Observation revealed a missing escutcheon ring in roam 304. These penetrations would allow smoke, fire and toxic gases to travel to unaffected areas on the building During the exit interview on October 3, 2024 at 0950, the manager stated she replace the missing escutcheon rings.”
“Based on observation and interview during the fire safety inspection process, the facility failed to ensure the facility's electric wiring was properly maintained. The facility census was sixty-two. This deficiency affected sixty-two of sixty-two residents. Observation revealed a ceiling light fixture hanging loose from the junction box in room 311 Observation revealed a ceiling light fixture hanging by it's wires in room 310. During the exit interview on October 3, 2024 at 0955, the manager stated stated she would have lights repaired. Missouri Department of Heaith and Senior Services City, Zip: Date of Survey: PLAN OF CORRECTION CrabApple Village Senior Estates Name: 214 Hartman Place St. Clair, MO 63077 10/3/2024 A2238 A2256 A2264 PROVIDER/SUPPLIER/CLIA IDENTIFICATION NUMBER This plan of correction submitted as required under State law. The submission of this POC does not constitute an admission on the part of CrabApple Village Senior Estates to the findings nor the conclusions drawn there from. The facility submission of part of the facility that the findings constitute a deficiency or the scope and severity regarding any of deficiencies cited is correctly applied. This exit now opens freely when code is entered. There are two other exits that were not obstructed remote to this exit door. This exit door only affected 24 residents and not 62. The total census for whole building is 62 but the floor where this door is located there is only 24 residents. This plan of correction submitted as required under State law. The submission of this POC does not constitute an admission on the part of CrabApple Village Senior Estates to the findings nor the conclusions drawn there from. The facility submission of part of the facility that the findings constitute a deficiency or the scope and severity regarding any of deficiencies cited is correctly applied. Exit light batteries were replaced and exit light is working properly. This exit light only affected the number of residents on that floor which was 38 residents. This plan of correction submitted as required under State law. The submission of this POC does not constitute an admission on the part of CrabApple Village Senior Estates to the findings nor the conclusions drawn there from. The facility submission of part of the facility that the findings constitute a deficiency or the scope and severity regarding any of deficiencies cited is correctly applied. Self-closure hinges were applied to the laundry room door and kitchen door in memory care. This only affected 24 residents, not 62. Self-closure hinges were applied to the main kitchen door. This only affected 38 residents, not 62 residents. This plan of correction submitted as required under State law. The submission of this POC does not constitute an admission on the part of CrabApple Village Senior Estates to the findings nor the conclusions drawn there from. The facility submission of ID PREFIX TAG PROVIDER'S PLAN OF CORRECTION: (EACH CORRECTIVE ACTION COMPLETION SHOULD BE CROSS-REFERENCED TO THE APPROPRIATE DEFICIENCY) DATE A2222 10/16/2024 10/15/2024 41/14/2024 11/7/2024 part of the facility that the findings constitute a deficiency or the scope and severity regarding any of deficiencies cited is correctly applied. Trim was replaced to the fire doors in the memory care. This only affected 24 residents and not 62 residents. This plan of correction submitted as required under State law. The submission of this POC does not constitute an admission on the part of CrabApple Village Senior Estates to the findings : nor the conclusions drawn there from. The facility submission of part of the facility that the findings constitute a deficiency or the scope and severity regarding any of deficiencies cited is correctly applied. Escutcheon ring was replaced to sprinkler heads in rooms 115 and 304 by Johnson Control. This plan of correction submitted as required under State law. The submission of this POC does not constitute an admission on the part of CrabApple Village Senior Estates to the findings nor the conclusions drawn there from. The facility submission of part of the facility that the findings constitute a deficiency or the scope and severity regarding any of deficiencies cited is correctly applied. Light fixture was resecured by Williams Electric in rooms 311 and 310. This citation only affected 24 residents and not 62. 10/29/2024 11/7/2024 The Administrator signing and dating the first page of the CMS-2567/State Form is indicating their approval of the plan of correction being submitted on this form.”
Read raw inspector notesClose inspector notes
PRINTED: 10/15/2024 FORM APPROVED Missouri Department of Health and Senior Services STATEMENT OF DEFICIENCIES (X1) PROVIDER/SUPPLIERICLIA (X2) MULTIPLE CONSTRUCTION (X93) DATE SURVEY AND PLAN OF CORRECTION IDENTIFICATION NUMBER: A. BUILDING: COMPLETED B.WING 10/03/2024 NAME OF PROVIDER OR SUPPLIER STREET ADDRESS, CITY, STATE, ZIP CODE 214 HARTMAN PLACE, SUITE 100 SAINT CLAIR, MO 63077 (X4) ID SUMMARY STATEMENT OF DEFICIENCIES PROVIDER'S PLAN OF CORRECTION (x5) PREFIX (EACH DEFICIENCY MUST BE PRECEDED BY FULL {EACH CORRECTIVE ACTION SHOULD BE COMPLETE TAG REGULATORY OR LSC IDENTIFYING INFORMATION) CROSS-REFERENCED TO THE APPROPRIATE DATE DEFICIENCY) CRAB APPLE VILLAGE SENIOR ESTATES : 19CSR 30-86.022(7)(A) Exits-2 per Floor-Remote/Unobstructed Exits, Stairways, and Fire Escapes. (A) Each floor of a facility shall have at least two (2) unobstructed exits remote from each other. Ill This regulation is not met as evidenced by: Class II Based on observation and interview during the fire safety inspection process, the facility failed to maintain unobstructed exits remote from each other. The facility census was sixty-two. This deficiency affected sixty-two of sixty-two residents. Observation revealed the exit door beyond the basement laundry is sticking, excessive force was required to open the door. During the exit interview on October 3, 2024 at 0930, the manager stated that they preferred the door be hard to open, due to it being in Memory Care, but would repair it if needed. 19 CSR 30-86.022(8)(C) Exit Sign-Illumination Exit Signs. (C) All required exit signs and directional indicators shall be positioned so that both normal and emergency lighting illuminates them. II/Iil This regulation is not met as evidenced by: Class III Based on observation and interview during the fire safety inspection process, the facility failed to ensure all exit signs were operational, The facility census was sixty-two. This deficiency affected ment of Health and Senior Services Missouri Dapg EG9SR11 If coniInuatibn s bel 10f6 STATE FORM Missouri Department of Health and Senior Services STATEMENT OF DEFICIENCIES (X1) PROVIGER/SUPPLIER/CLIA AND PLAN OF CORRECTION (DENTIFICATION NUMBER: A. BUILDING: B. WING NAME OF PROVIDER OR SUPPLIER CRAB APPLE VILLAGE SENIOR ESTATES SAINT CLAIR, MO 63077 SUMMARY STATEMENT OF DEFICIENCIES (EACH DEFICIENCY MUST BE PRECEDED BY FULL REGULATORY OR LSC IDENTIFYING INFORMATION) (X4) ID PREFIX TAG Continued From page 1 | sixty-two of sixty-two residents. Observation revealed an exit sign/emergency light that would illuminate while depressing the test button, but only for a couple of seconds before it failed, in the dining room. During the exit interview on October 3, 2024 at 0935, the manager stated she would have the exit sign repaired, 19 CSR 30-86.022(10}(A) Hazardous Area Requirements Protection from Hazards. {A) In assisted living facilities and residential care facilities licensed on or after November 13, 1980, for more than twelve (12) beds, hazardous areas shall be separated by construction of at least a one- (1-) hour fire-resistant rating. In facilities equipped with a complete fire alarm system, the one- (1-) hour fire separation is required only for furnace or boiler rooms. Hazardous areas equipped with a complete sprinkler system are not required to have this one- (1-) hour fire separation. Doors to hazardous areas shall be self-closing and shail be kept closed unless an electromagnetic hold-open device is used which is interconnected with the fire alarm system. When the sprinkler option is chosen, the areas shall be separated from other spaces by smoke-resistant partitions and doors. The doors shall be self-closing or automatic-closing. Facilities formerly licensed as residential care facility | or Il, and existing prior to November 13, 1980, shall be exempt from this requirement. II This regulation is not met as evidenced by: : Class Il Missouri Department of Health and Senior Services STATE FORM 6e29 EG9R11 (X2) MULTIPLE CONSTRUCTION PRINTED: 10/15/2024 FORM APPROVED (X3) DATE SURVEY COMPLETED 10/03/2024 STREET ADDRESS, CITY, STATE, ZIP CODE 214 HARTMAN PLACE, SUITE 100 PROVIDER'S PLAN OF CORRECTION (EACH CORRECTIVE ACTION SHOULD BE CROSS-REFERENCED TO THE APPROPRIATE DEFICIENCY) (x5) COMPLETE DATE If continuation sheet 2 of 6 PRINTED; 10/45/2024 FORM APPROVED Missouri Department of Health and Senior Services STATEMENT OF DEFICIENCIES (X1) PROVIDER/SUPPLIER/CLIA (X2) MULTIPLE CONSTRUCTION (X3) DATE SURVEY AND PLAN OF CORRECTION IDENTIFICATION NUMBER: A. BUILDING: COMPLETED BWINGO 10/03/2024 NAME OF PROVIDER OR SUPPLIER STREET ADDRESS, CITY, STATE, ZIP CODE 214 HARTMAN PLACE, SUITE 100 SAINT CLAIR, MO 63077 (x4) 1D SUMMARY STATEMENT OF DEFICIENCIES PROVIDER'S PLAN OF CORRECTION (x5) PREFIX (EACH DEFICIENCY MUST BE PRECEDED BY FULL (EACH CORRECTIVE ACTION SHOULD BE COMPLETE TAG REGULATORY OR LSG IDENTIFYING INFORMATION} CROSS-REFERENCED TO THE APPROPRIATE DATE DEFICIENCY) CRAB APPLE VILLAGE SENIOR ESTATES Continued From page 2 Based on observation and interview during the fire safety inspection process on November 15, 2023 the facility failed to properly maintain a self-closing smoke partition door to hazardous areas that separate them from the residential spaces. The facility census was sixty-two. This deficiency affected sixty-two of sixty-two residents. Observation revealed the self-closure devices on the laundry room smoke partition doors were not adjusted properly to close the doors. Observation revealed the self-closure device on the kitchen scullery smoke partition door was not properly adjusted to close the door Observation revealed no self-closure device on the main kitchen smoke partition.door. Observation reveled the kitchen window was 2 shutter style doors that were not self-closing, nor attached to the fire alarm, and are not smoke partitions. During the exit interview on October 3, 2024 at 0940, the manager stated that the window was approved in plan review and has always been this way. She stated she would have maintenance adjust the doors on all the faundry rooms and kitchen, plus install a self-closure device on the other kitchen door. 19 CSR 30-86.022(10)(I} Smoke Section Partitions > than 20 beds Protection from Hazards. (!) In facilities whose plans were approved ar Missouri Department of Health and Senior Services STATE FORM e699 EGOR11 If continuation sheet 3 of 6 PRINTED: 10/15/2024 FORM APPROVED Missouri Department of Health and Senior Services STATEMENT OF DEFICIENCIES (X1) PROVIDER/SUPPLIER/CLIA {X2) MULTIPLE CONSTRUCTION (X3) DATE SURVEY AND PLAN OF CORRECTION IDENTIFICATION NUMBER: A. BUILDING: COMPLETED B. WING 10/03/2024 NAME OF PROVIDER OR SUPPLIER STREET ADDRESS, CITY, STATE, ZIP CODE 214 HARTMAN PLACE, SUITE 100 SAINT CLAIR, MO 63077 (X4) ID SUMMARY STATEMENT OF DEFICIENCIES PROVIDER’S PLAN OF CORRECTION {X5) PREFIX (EACH DEFICIENCY MUST BE PRECEDED BY FULL (EACH CORRECTIVE ACTION SHOULD BE COMPLETE TAG REGULATORY OR LSC IDENTIFYING INFORMATION) 1 CROSS-REFERENCED TO THE APPROPRIATE DATE DEFICIENCY} CRAB APPLE VILLAGE SENIOR ESTATES Continued From page 3 which were initially licensed after December 31, 1987, for more than twenty (20) beds and all facilities licensed after August 28, 2007, each smoke section shall be separated by one- (1-) hour fire-rated smoke partitions. The smoke partitions shail be continuous from outside wall-to-outside wall and from floor-to-floor or floor-to-roof deck. All doors in this wall shall be at least twenty- (20-) minute fire-rated or its equivalent, self-closing, and may be held open only if the door closes automatically upon activation of the complete fire alarm system. I! This regulation is not met as evidenced by: Class || Based on observation and interview during the fire safety inspection process, the facility, licensed after December 31, 1987 for more than twenty (20) beds, failed to ensure doors in a smoke partition closed completely. The facility census was sixty-two. This deficiency affected sixty-two of sixty-two residents. Observation of a smoke door next to room 308 revealed that the smoke doors missing the trim, leaving a noticeable gap between the doors. Smoke doors failing to close completely will allow smoke and toxic gases to spread to other areas of the building. During the exit interview on October 3, 2024 at 0945, the manager stated that they would have the door repaired. 19 CSR 30-86.022(11)(B) Sprinkler System Maintenance/Testing Missouri Department of Health and Senior Services STATE FORM 5ae8 EGSR11 IF continuation sheet 4 of 6 PRINTED; 10/15/2024 FORM APPROVED Missouri Department of Health and Senior Services STATEMENT OF DEFICIENCIES (%1} PROVIDER/SUPPLIER/CLIA (X2) MULTIPLE CONSTRUCTION (X3) DATE SURVEY AND PLAN OF CORRECTION IDENTIFICATION NUMBER: A. BUILDING: COMPLETED BWING 10/03/2024 NAME OF PROVIDER OR SUPPLIER STREET ADDRESS, CITY, STATE, ZIP CODE 214 HARTMAN PLACE, SUITE 100 SAINT CLAIR, MO 63077 (x4) ID SUMMARY STATEMENT OF DEFICIENCIES PROVIDER'S PLAN OF CORRECTION (5) PREFIX (EACH DEFICIENCY MUST BE PRECEDED @Y FULL : (EACH CORRECTIVE ACTION SHOULD BE COMPLETE TAG REGULATORY OR LSC IDENTIFYING INFORMATION) CROSS-REFERENCED TO THE APPROPRIATE DATE DEFICIENCY) : CRAB APPLE VILLAGE SENIOR ESTATES Continued From page 4 Sprinkler Systems. (B) Facilities that have a sprinkler system installed prior to August 28, 2007, shall inspect, maintain, and test these systems in accordance with the requirements that were in effect for such facilities on August 27, 2007. I/II This regulation is not met as evidenced by: Class JI Based on observation and interview during the fire safety inspection process, the facility failed to maintain a complete sprinkler system in accordance with NFPA 13, 1999 edition. The facility census was sixty-two. This deficiency affected sixty-two of sixty-two residents. Observation revealed a missing escutcheon ring in roam 115. Observation revealed a missing escutcheon ring in roam 304. These penetrations would allow smoke, fire and toxic gases to travel to unaffected areas on the building During the exit interview on October 3, 2024 at 0950, the manager stated she replace the missing escutcheon rings. 19 CSR 30-86.032(13) Electrical Wiring, Maintained, Inspected In facilities that are constructed or have plans approved after July 1, 2005, electrical wiring shall be installed and maintained in accordance with the requirements of the National Electrical Code, 1999 edition, National Fire Protection Association, Missouri Department of Heallh and Senior Services STATE FORM p90 EGOR11 If continuation sheet 5 of 6 PRINTED: 10/15/2024 FORM APPROVED Missouri Department of Health and Senior Services STATEMENT OF DEFICIENCIES (X1) PROVIDER/SUPPLIER/CLIA (X2) MULTIPLE CONSTRUCTION (X3) DATE SURVEY AND PLAN OF CORRECTION IDENTIFICATION NUMBER: A. BUILDING: COMPLETED B.WING 10/03/2024 NAME OF PROVIDER OR SUPPLIER STREET ADDRESS, CITY, STATE, ZIP CODE 214 HARTMAN PLACE, SUITE 100 SAINT CLAIR, MO 63077 (X4) ID SUMMARY STATEMENT OF DEFICIENCIES PROVIDER'S PLAN OF CORRECTION (x5) PREFIX (EACH DEFICIENCY MUST BE PRECEDED BY FULL (EACH CORRECTIVE ACTION SHOULD BE COMPLETE TAG REGULATORY OR LSC IDENTIFYING INFORMATION) CROSS-REFERENCED TO THE APPROPRIATE DATE DEFICIENCY) CRAB APPLE VILLAGE SENIOR ESTATES Continued From page 5 Inc., incorporated by reference, in this rule and available by mail at One Batterymarch Park, Quincy, MA 02269, and local codes. This rule does not incorporate any subsequent amendments or additions to the materials incorporated by reference, Facilities built between September 28, 1979 and July 4, 2005 shall be maintained in accordance with the requirements of the National Electrical Code, which was in effect at the time of the original plan approval and local codes. This rule does not incorporate any subsequent amendments or additions. In facilities built prior to September 28, 1979, electrical wiring shall be maintained in good repair and shall not present a safety hazard. All facilities shall have wiring inspected every two (2) years by a qualified electrician. II/Ill This regulation is not met as evidenced by: Class II] Based on observation and interview during the fire safety inspection process, the facility failed to ensure the facility's electric wiring was properly maintained. The facility census was sixty-two. This deficiency affected sixty-two of sixty-two residents. Observation revealed a ceiling light fixture hanging loose from the junction box in room 311 Observation revealed a ceiling light fixture hanging by it's wires in room 310. During the exit interview on October 3, 2024 at 0955, the manager stated stated she would have lights repaired. Missouri Department of Heaith and Senior Services STATE FORM 5098 EGSR11 If continuation sheet 6 of 6 Street Address, City, Zip: Date of Survey: PLAN OF CORRECTION CrabApple Village Senior Estates Name: 214 Hartman Place St. Clair, MO 63077 10/3/2024 A2238 A2256 A2264 PROVIDER/SUPPLIER/CLIA IDENTIFICATION NUMBER This plan of correction submitted as required under State law. The submission of this POC does not constitute an admission on the part of CrabApple Village Senior Estates to the findings nor the conclusions drawn there from. The facility submission of part of the facility that the findings constitute a deficiency or the scope and severity regarding any of deficiencies cited is correctly applied. This exit now opens freely when code is entered. There are two other exits that were not obstructed remote to this exit door. This exit door only affected 24 residents and not 62. The total census for whole building is 62 but the floor where this door is located there is only 24 residents. This plan of correction submitted as required under State law. The submission of this POC does not constitute an admission on the part of CrabApple Village Senior Estates to the findings nor the conclusions drawn there from. The facility submission of part of the facility that the findings constitute a deficiency or the scope and severity regarding any of deficiencies cited is correctly applied. Exit light batteries were replaced and exit light is working properly. This exit light only affected the number of residents on that floor which was 38 residents. This plan of correction submitted as required under State law. The submission of this POC does not constitute an admission on the part of CrabApple Village Senior Estates to the findings nor the conclusions drawn there from. The facility submission of part of the facility that the findings constitute a deficiency or the scope and severity regarding any of deficiencies cited is correctly applied. Self-closure hinges were applied to the laundry room door and kitchen door in memory care. This only affected 24 residents, not 62. Self-closure hinges were applied to the main kitchen door. This only affected 38 residents, not 62 residents. This plan of correction submitted as required under State law. The submission of this POC does not constitute an admission on the part of CrabApple Village Senior Estates to the findings nor the conclusions drawn there from. The facility submission of ID PREFIX TAG PROVIDER'S PLAN OF CORRECTION: (EACH CORRECTIVE ACTION COMPLETION SHOULD BE CROSS-REFERENCED TO THE APPROPRIATE DEFICIENCY) DATE A2222 10/16/2024 10/15/2024 41/14/2024 11/7/2024 part of the facility that the findings constitute a deficiency or the scope and severity regarding any of deficiencies cited is correctly applied. Trim was replaced to the fire doors in the memory care. This only affected 24 residents and not 62 residents. This plan of correction submitted as required under State law. The submission of this POC does not constitute an admission on the part of CrabApple Village Senior Estates to the findings : nor the conclusions drawn there from. The facility submission of part of the facility that the findings constitute a deficiency or the scope and severity regarding any of deficiencies cited is correctly applied. Escutcheon ring was replaced to sprinkler heads in rooms 115 and 304 by Johnson Control. This plan of correction submitted as required under State law. The submission of this POC does not constitute an admission on the part of CrabApple Village Senior Estates to the findings nor the conclusions drawn there from. The facility submission of part of the facility that the findings constitute a deficiency or the scope and severity regarding any of deficiencies cited is correctly applied. Light fixture was resecured by Williams Electric in rooms 311 and 310. This citation only affected 24 residents and not 62. 10/29/2024 11/7/2024 The Administrator signing and dating the first page of the CMS-2567/State Form is indicating their approval of the plan of correction being submitted on this form.
Source: Missouri Dept. of Health and Senior Services · Section for Long-Term Care Regulation. DHSS inspection portal →